Woodward 8516-039 TG-13 Turbine Governor
Delivery time 3 days
Product origin New/used
Email plcru@foxmail.com
Mobile/wechat /WhatsApp +86 18185397189
The Woodward 8516-039 (TG-13) is a mechanical-hydraulic differential speed gover
Core Positioning and Working Principle
Type: Mechanical-Hydraulic, Speed Droop, does not support isochronous operation.
Speed Measurement: The turbine speed is directly detected by the internal flyweight/ball joint mechanism driven by the input drive shaft.
Control Logic: Speed measurement → Comparison with set speed → Hydraulic amplification → Output shaft rotation → Adjustment of turbine inlet valve opening → Stabilization of speed (Woodward).
Hydraulic System: Integrated oil sump and gear pump, independent oil supply (1034 kPa / 150 psi), no external hydraulic station required.
Output: Rotate the output shaft (maximum angle 40°, recommended stroke from no-load to full-load is 2/3 of the full stroke), directly driving the speed control valve.
Key Technical Parameters (8516-039 Original Factory Calibration)
Order Number: 8516-039 (TG-13 Series, 4000 CCW, ATEX Certified) Woodward
Applicable Speed: 2400–4000 RPM (CCW rotation direction, other ranges can be customized) Woodward
Output Torque: 12 ft-lb (16.3 N·m) (Maximum)
Speed Accuracy: Steady State ±0.2%; ±0.1% under Load Variation
Response Time: 5% Speed Step Change ≤0.5 s
Droop Rate: 2%–6% (Adjustable, Typical Factory Rate 4%)
Overspeed Protection: Mechanical Trip, 115% Rated Speed (Adjustable)
Internal Oil Pressure: 1034 kPa (150 psi)
Output Shaft: 1/2-inch Serrated Shaft, Extends on Both Sides
Material: Die-cast Aluminum Housing (Lightweight, Corrosion Resistant)
Environment: Operating Temperature -20°C to +60°C; Humidity 5%–95% RH (non-condensing); ATEX explosion-proof certified. Weight: Approx. 14.5 lb (6.6 kg).