The following is the content of the data table of Emerson IC695ALG508-RX3i Isola
The following is the content of the data table of Emerson IC695ALG508-RX3i Isolated RTD Input module:
Overview:
Product Positioning: Resistance Temperature Detector (RTD) input module for the PACSystem RX3i programmable Automation Controller (PAC) platform.
Manufacturer: Emerson Automation, formerly known as GE Intelligent Platform (GE IP).
Channel characteristics:
Number of channels: 8 isolated differential input channels.
Wiring method: Each channel can be configured as a 2-wire, 3-wire or 4-wire RTD sensor input.
Supported types:
RTD types: Supports RTD types such as platinum 385, platinum 391.6, nickel 618, nickel 672, nickel iron 518, and copper 426.
Resistance range: Compatible with direct resistance input, the range is 0-260, 0-525, 0-1050, 0-2100, 0-3150, 0-4200 ohms.
Data characteristics:
Data format: It can be configured as 16-bit integer or 32-bit real number data format.
Measurement units: Celsius, Fahrenheit or ohm are optional.
Fault monitoring: including watchdog, random access memory (RAM) fault and flash memory fault status monitoring.
Electrical characteristics:
Power consumption: Maximum 2.5W.
Internal power supply: 3.3V/400mA 5.1V/200mA.
Mechanical characteristics:
Dimensions: 200×150×20mm.
Weight: 1.8kg.
Installation method: DIN rail installation.
Environmental characteristics:
Operating temperature: 0-60℃.
Storage temperature: -40-85℃.
Humidity: 5-95%, non-condensing.
Other features:
Hot plugging function: It supports hot plugging, allowing modules to be removed and inserted while the system is running without affecting the normal operation of the system.