Bently Nevada 330301-00-16-10-90-01-00 high-temperature probe
Delivery time 3 days
Product origin New/used
Email plcru@foxmail.com
Mobile/wechat /WhatsApp +86 18185397189
I. Model Segment Explanation330301: 3/4-16 UNF Threaded 3300 XL High Temperature
I. Model Segment Explanation
330301: 3/4-16 UNF Threaded 3300 XL High Temperature Eddy Current Probe Body
00: No Thread Extension Length (0 inches)
16: Total Probe Housing Length 1.6 inches
10: Stainless Steel Hard Wire Cable Length 1 meter
90: Total System Length 9 meters
01: Extension Cable with Stainless Steel Metal Armor
00: No Explosion-Proof Certification Required
II. Electrical Performance Parameters
Measurement Range: Linear range 4mm (160mil), suitable for high-temperature unit radial vibration, axial thrust, and differential expansion monitoring
Standard Sensitivity: 7.87V/mm (200mV/mil), factory-calibrated, no field calibration required
Frequency Response Range: DC to 10kHz, covering the conventional vibration frequency range of steam turbines and gas turbines
Cable Electrical Characteristics: Extension cable impedance 75Ω, capacitance 69.9pF per meter; 9 The entire system impedance and capacitors are factory-matched.
Connection Interface: ClickLoc miniature coaxial quick-lock connector, stainless steel connector material. Recommended torque for mating is to tighten by hand and then rotate 1/8 turn.
Matching: Must be paired with a high-temperature preamplifier of the same total length (replacement model 330380-90-00, the original 330300 is discontinued).
III. Mechanical Structure and Materials
Probe Sensing Terminal: Sealed ceramic material, hermetically sealed, waterproof, oily, and impurity resistant.
Probe Housing: AISI 316L stainless steel, high temperature and corrosion resistant.
Rigid Hardwire Cable: AISI 304L stainless steel sheath, fixed length 1 meter.
Extension Cable: FEP insulated triaxial cable, with stainless steel armor protection.
Installation Thread: Standard 3/4-16 UNF external thread.
Maximum Installation Tightening Torque: Probe housing 81 N·m (720 in·lb)
Mechanical Tensile Strength Withstand: Maximum tensile strength at the probe and extension cable connection point 289 N (65 mm). (lbs)
Minimum bending radius: Minimum cable bending radius 25.4mm (1 inch)
Weight reference: Hard wire cable 117g per meter, probe housing 12g per centimeter; total transport weight of 9 meters including armor is approximately 2.5kg
IV. Temperature environmental tolerance
Probe body (including 1 meter hard wire): Unified operating and storage temperature range -34℃ ~ +350℃, capable of continuous operation at 350℃ for extended periods.
Armored extension cable: Operating temperature -52℃ ~ +177℃
Matching high-temperature preamplifier 330380-90-00: Operating temperature -52℃~+100℃, storage temperature -52℃~+105℃, preamplifier aluminum shell with epoxy powder coating protection
Humidity tolerance: Stable operation in environments with up to 95% condensation resistance
Interference protection: Excellent RFI/EMI protection Radio frequency electromagnetic interference immunity; single-point shielded grounding is recommended.
V. Application Scenarios and Basic Information
Applicable Equipment: Gas turbines, steam turbine high-temperature sealed areas, bearing high-temperature measuring points, interstage clearance, rotor mid-span vibration mode monitoring, differential expansion axial displacement measurement
Factory Configuration: Probe + 1 meter stainless steel hard wire + 8 meter armored extension cable. The entire set is factory-calibrated and cannot be arbitrarily disassembled or mixed with preamplifiers of different lengths.
Warranty: Original factory standard 12-month warranty
Origin: Manufactured in Bently Nevada, a subsidiary of Baker Hughes, USA
Explosion-proof Certification: This model does not have explosion-proof certification (code 00). For explosion-proof applications, a model with a certification code must be used.
VI. Usage Restrictions
The total length of the entire set is strictly limited to 9 meters. Do not cut or splice the cable on-site, as this will damage the factory-installed capacitance impedance matching and directly cause sensitivity drift and measurement failure. Ceramic terminals must not be impacted or bumped; damage will result in loss of airtightness and high-temperature resistance. Avoid cutting the sheath with sharp edges when laying armored cables; do not allow direct contact with high-temperature pipe walls for baking in high-temperature areas. Only compatible with 3300 XL high-temperature series preamplifiers; cannot be used with standard 8mm/5mm preamplifiers at room temperature.